Fluke 1507 Insulation Resistance Tester

  • Rugged, compact advanced insulation resistance tester for electrical contractors and industrial and commercial electricians
  • Automatically calculates Polarization Index and Dielectric Absorption Ratio
  • Makes repetitive tests simple and easy with a Compare (Pass/Fail) function
  • Offers multiple insulation test voltages: 50 V, 100 V, 250 V, 500 V, and 1000 V

Contact for price

Add to Wishlist
Add to Wishlist

Description

AC/DC Voltage Measurement
Accuracy Range 600.0 V
Resolution 0.1 V
50 Hz to 400 Hz ± (% of Rdg + Digits) ±(2% + 3)
Input impedance 3 MΩ (nominal), < 100 pF
Common mode rejection ratio (1 kΩ unbalanced): > 60 dB at DC, 50 or 60 Hz
Overload protection 600 V rms or DC
Earth Bond Resistance Measurement
Range/Resolution 20.00 Ω 0.01 Ω
200.0 Ω 0.1 Ω
2000 Ω 1.0 Ω
20.00 kΩ 0.01 kΩ
Accuracy ±(1.5% + 3)
Overload protection 2 V rms or DC
Open circuit test voltage > 4.0 V, < 8 V
Short circuit current > 200.0 mA
Insulation Specifications
Measurement range 0.01 MΩ to 10 GΩ
Test voltage 50 V, 100 V, 250 V, 500 V, 1000 V
Test voltage accuracy + 20%, – 0%
Short circuit current 1 mA nominal
Auto discharge Discharge time < 0.5 second for C = 1 µF or less
Live circuit indicator Inhibit test if terminal voltage > 30 V prior to initialization of test
Maximum capacitive load Operable with up to 1 µF load
Measure accuracy 50 V ±(3% + 5)
100 V ±(3% + 5)
250 V ±(1.5% + 5)
500 V ±(1.5% + 5)
1000 V ±(1.5% + 5) to 2000 MΩ, ±(10% + 3) above 2000 MΩ
General Specifications
Maximum voltage applied to any terminal: 600 V AC rms or DC
Storage temperature -40°C to 60°C (-40°F to 140°F)
Operating temperature -20°C to 55°C (-4°F to 131°F)
Temperature coefficient 0.05 x (specified accuracy) per °C for temperatures < 18°C or > 28°C (< 64°F or > 82°F)
Relative humidity
0% to 95% @ 10°C to 30°C (50°F to 86°F)
0% to 75% @ 30°C to 40°C (86°F to 104°F)
0% to 40% @ 40°C to 55°C (104°F to 131°F)
Vibration Random, 2 g, 5-500 Hz per MIL-PRF-28800F, Class 2 instrument
Shock 1 meter drop per IEC 61010-1 2nd Edition (1 meter drop test, six sides, oak floor)
Electromagnetic compatibility In an RF field of 3 V/M, accuracy = specified accuracy (EN 61326-1:1997)
Safety Complies with ANSI/ISA 82.02.01 (61010-1) 2004, CAN/CSA-C22.2 NO. 61010-1-04, and IEC/EN 61010-1 2nd Edition for measurement category IV 600 V (CAT IV)
Certifications CSA per standard CSA/CAN C22.2 No. 61010.1-04; TUV per standard IEC/EN 61010-1 2nd Edition
Batteries Four AA batteries (NEDA 15A or IEC LR6)
Battery life Insulation test use: Tester can perform at least 1000 insulation tests with fresh alkaline batteries at room temperature. These are standard tests of 1000 V into 1 MΩ with a duty cycle of 5 seconds on and 25 seconds off.
Resistance measurements: Tester can perform at least 2500 earth bond resistance measurements with fresh alkaline batteries at room temperature. These are standard tests of 1 Ω with a duty cycle of 5 seconds on and 25 seconds off.
Size (H x W x L) 5.0 x 10.0 x 20.3 cm (1.97 x 3.94 x 8.00 in)
Weight 550 g (1.2 lb)
IP rating IP40
Altitude Operating 2000 m CAT IV 600 V, 3000 m CAT III 600 V
Non-operating (storage) 12,000 m
Over-range capability 110% of range
Included accessories TL224 Test Leads, TP74 Test Probes, clips PN 1958654 (red) and PN 1958646 (black), holster and remote probe